(2) Table 8.5 shows the procedure used to change manually from equalized charge to
floating charge.
After the charging mode has been changed to equalized charge using the procedure
on the previous page, the mode will automatically change back to floating charge after
a set period of time has elapsed. Therefore, normally there is no need to change the
mode manually as described below.
Table 8.6
Step
Procedure
1
Check to make sure
that the "EQUAL
CHARGE" LED is lit.
2
Hold down the "FLOAT
/ EQUAL" key (
Figure 6.3.1 on page
14) for at least 0.5
second.
→ Change to floating
charge is complete.
Changing From Equalized Charge to Floating Charge
LCD/LED Status (After Execution)
UPS SUPPLY
~
~
AC INPUT
CONVERTER
FLOAT CHARGE
BATTERIES
EQUAL CHARGE
DISCHARGE
~
BYPASS INPUT
in
UPS SUPPLY
~
~
AC INPUT
CONVERTER
FLOAT CHARGE
BATTERIES
EQUAL CHARGE
DISCHARGE
~
BYPASS INPUT
The "FLOAT CHARGE" LED lit.
The "EQUAL CHARGE" LED unlit.
- 38 -