Setting The Profibus Address - Siemens SIMATIC ET 200X Manual

Distributed i/o device
Table of Contents

Advertisement

Procedure for BM 141, BM 142 and BM 147/CPU
1. Remove the connector plate from the basic module before you set the
PROFIBUS address. The DIL switches are concealed by the connector plate.
2. Set the PROFIBUS address using the DIL switches.
The diagram below shows the location of the DIL switches in the basic module as
well as an example of the switch settings.
Figure 3-11
Note: The PROFIBUS address in the basic module must always correspond to the
PROFIBUS address specified in the configuration software for this ET 200X.
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06

Setting the PROFIBUS address

Example: PROFIBUS address 78
1
2
3
6
2
+2
+ 2
+ 2
= 2 + 4 + 8 + 64 = 78
ON
1
2
3
4
5
* Switch 8 must be OFF!
Installation
6
7
8*
3-17