Door Interlock System; Replacing The Precharging Transformer - Siemens SINAMICS SM150 6SL3810-7NN38-0AA1 Operating And Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

Maintenance
9.5 Repair
9.5.9

Door interlock system

Contact Technical Support (Page 171) if the door interlock system becomes defective.
9.5.10

Replacing the precharging transformer

Danger to life as a result of incorrect replacing the precharging transformer
Replacing the precharging transformer incorrectly can result in death, serious injury, or
material damage.
● Follow "the five safety rules (Page 15)".
● Before replacing the precharging transformer, open the safety disconnector for the 400 V
● Lift the transformer carefully because it is heavy (> 45 kg).
Removing the precharging transformer
1. Detach the high-voltage cables
2. Detach the 400 V connecting cables
3. Detach the grounding cable
4. Remove the fixing screws
5. Remove the transformer.
164
WARNING
supply.
.
.
.
at the front and rear on the base brackets.
Operating Instructions Rev.201910281406 EXAMPLE
SINAMICS SM150 6SL3810-7NN38-0AA1