External Safety Components; Protection And Monitoring Functions Of Internal Components - Siemens SINAMICS SM150 6SL3810-7NN38-0AA1 Operating And Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

Description
3.2 Safety concept
3.2.2

External safety components

The following external components for the safety concept are provided:
● Circuit breaker
● Input-side transformer
● Filter mats
3.2.3

Protection and monitoring functions of internal components

The internal components have the following protection and monitoring functions:
● Crowbar
● Device protection using monitoring systems:
● Differential pressure monitor (fan failure, blocked filter mats)
● Shutdown in the event of semiconductor failure
● Shutdown in the event of control component failure
● Internal protection functions for the control hardware
● Protection against communication failure between the closed-loop control and the power
● Anti-condensation heating
28
More detailed information is provided in Chapter Circuit-breaker (provided by the customer)
(Page 36).
The transformer on the input side must be configured in such a way that the maximum short-
circuit current is not exceeded. Information on this is provided in the technical data sheet of
the transformer.
Use only approved filter mats as spare part.
– Current monitoring
– DC link monitoring
– Output voltage monitoring
– Thermal monitoring of the power unit
– Precharge monitoring
– Insulation monitoring
– Supply voltage monitoring
– GSV monitoring
– Circuit-breaker monitoring
unit
SINAMICS SM150 6SL3810-7NN38-0AA1