2.3 Quick commissioning
The following descriptions show how to set up the drive using the quick commissioning wizard, which is
integrated in the BOP-2.
Starting quick commissioning
• Press ESC to enter the menu selection
• Use UP and DOWN to move the menu bar to SETUP and press OK
• The screen will automatically display the next parameter in the commissioning sequence
Quick commissioning now starts. It will help you to set all of the relevant parameters step-by-step.
Parameters that are not relevant will be skipped automatically. This allows you to adjust the factory
settings of your converter to the requirements of your motor.

Resetting the converter

• Press OK while the BOP-2 shows RESET
• Press UP or DOWN to change the value to YES
• Press OK and wait until the BUSY symbol disappears
• All values have now been reset to the factory setting
Operator Panels BOP-2 and IOP-2:
32
ESC
OK
Quick commissioning
OK
OK
Any step of the commissioning
wizard can be skipped by press-
ing the DOWN button. You can
go back one step by pressing
the UP button. By confirming
one step with OK, the screen will
automatically display the next
parameter in the commissioning
sequence.