Technical Data

Auxiliary voltage
Power input
Line-side fuse
Alarm relay (DR)
Connection
Switching current (continuous)
Switching voltage
Switching capacity
3-way terminal
Minimum cross-section of the wires for
auxiliary voltage and earth (ground)
Nominal conductor cross-section
Tightening torque
Stripping length:
FO connection
Connection method
Wavelength
Fibre Type
Baud rate
Protocol
Laser class
Transmit power in dBm , peak (type),
NA = 0.275
Max. optical power for high level
Min. optical power for low level
Optical power budget
NA = 0.275
Range
Ethernet interface
Connection
TCP/IP
RS232 and RS485
SIEMENS AG
24 V – 250 V DC +/-20 %
60 V – 230 V AC +/-20 % , 45-65 Hz,
2.5 W DC
14 VA AC
T 2A/250 V AC and 250 V DC
acc. to IEC 60127
Relays, 1 NC isolated
2-way screw terminal,
1A
250V AC and DC
20 W / 20 VA
2
1.5 mm
2.5 mm² , rigid conductor or with wire
end ferrule
0.5 Nm
up to 8 mm
ST connector receiver and transmitter
820 nm
Multimode fibre, 62.5/125 µm
2400 up to max. 115200 baud
full-duplex
1 acc. to EN60825-1/-2
fibre 62.5/125 µm
-12.0 (fibre type 62.5/125 µm)
Max. -40 dBm peak
Min.: -24 dBm peak
Min. 8 dB (62.5/125 µm)
Max. 2 Km (attenuation 3 dB / Km 62.5 µm)
Max. 2 m with plastic fibre
10BaseT (10/100 Mbits)
RJ45, screened, 8-way
UDP Port 3497 (User Datagram Protocol)
ICMP (Internet Control Message Protocol)
ARP (Address Resolution Protocol)