Daikin VRV II RXYQ5MATL Service Manual page 36

R-410a heat pump 60hz
Table of Contents

Advertisement

Si39-504
Ceiling Mounted Cassette Corner Type
Model
1 Cooling Capacity (19.5°CWB)
2 Cooling Capacity (19.0°CWB)
3 Heating Capacity
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
5 Sound Level (H/L) (220V)
Safety Devices
Refrigerant Control
Connectable Outdoor Units
Model
Panel Color
Decoration
Dimensions: (H×W×D)
Panels
(Option)
Air Filter
Weight
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference :
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1m in front of the unit and 1m downward.
Specifications
FXKQ25MVE
kcal/h
2,500
Btu/h
9,900
kW
2.9
kW
2.8
kcal/h
2,800
Btu/h
10,900
kW
3.2
Galvanized Steel Plate
mm
215×1,110×710
mm
2×11×1.75
0.180
3D12H1AN1V1
Sirocco Fan
W
15×1
m³/min
11/9
50
Hz
cfm
388/318
m³/min
11/8.5
60
Hz
cfm
388/300
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyethylene Foam
φ6.4 (Flare Connection)
mm
φ12.7 (Flare Connection)
mm
VP25
mm
External Dia. 32
(
Internal Dia. 25
kg
31
dBA
38/33
Fuse.
Thermal Fuse for Fan Motor.
Electronic Expansion Valve
R-410A M(A) Series
BYK45FJW1
White (10Y9/0.5)
mm
70×1,240×800
Resin Net
(with Mold Resistant)
kg
8.5
Operation Manual.
Installation Manual. Paper
Pattern for Installation. Drain
Hose. Clamp Metal.
Insulation for Fitting. Sealing
Pads. Clamps. Screws.
Washers. Positioning Jig for
Installation. Insulation for
Hanger Bracket. Air Outlet
Blocking Pad.
difference : 0m.
difference : 0m.
0m. (Heat pump only)
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
FXKQ32MVE
3,200
12,600
3.7
3.6
3,400
13,600
4.0
Galvanized Steel Plate
215×1,110×710
2×11×1.75
0.180
3D12H1AN1V1
Sirocco Fan
15×1
11/9
388/318
11/8.5
388/300
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Polyethylene Foam
φ6.4 (Flare Connection)
φ12.7 (Flare Connection)
VP25
External Dia. 32
)
(
)
Internal Dia. 25
31
38/33
Fuse.
Thermal Fuse for Fan Motor.
Electronic Expansion Valve
R-410A M(A) Series
BYK45FJW1
White (10Y9/0.5)
70×1,240×800
Resin Net
(with Mold Resistant)
8.5
Operation Manual.
Installation Manual. Paper
Pattern for Installation. Drain
Hose. Clamp Metal.
Insulation for Fitting. Sealing
Pads. Clamps. Screws.
Washers. Positioning Jig for
Installation. Insulation for
Hanger Bracket. Air Outlet
Blocking Pad.
C : 3D038813
FXKQ40MVE
4,000
16,000
4.7
4.5
4,300
17,100
5.0
Galvanized Steel Plate
Galvanized Steel Plate
215×1,110×710
2×11×1.75
0.180
3D12H1AP1V1
Sirocco Fan
20×1
13/10
459/353
13/10
459/353
Direct Drive
Microprocessor Thermostat
Microprocessor Thermostat
for Cooling and Heating
for Cooling and Heating
Polyethylene Foam
Polyethylene Foam
φ6.4 (Flare Connection)
φ9.5 (Flare Connection)
φ12.7 (Flare Connection)
φ15.9 (Flare Connection)
VP25
External Dia. 32
External Dia. 32
(
)
(
Internal Dia. 25
31
40/34
Fuse.
Thermal Fuse for Fan Motor.
Thermal Fuse for Fan Motor.
Electronic Expansion Valve
Electronic Expansion Valve
R-410A M(A) Series
R-410A M(A) Series
BYK45FJW1
White (10Y9/0.5)
White (10Y9/0.5)
70×1,240×800
Resin Net
(with Mold Resistant)
(with Mold Resistant)
8.5
Operation Manual.
Operation Manual.
Installation Manual. Paper
Installation Manual. Paper
Pattern for Installation. Drain
Pattern for Installation. Drain
Hose. Clamp Metal.
Hose. Clamp Metal.
Insulation for Fitting. Sealing
Insulation for Fitting. Sealing
Pads. Clamps. Screws.
Pads. Clamps. Screws.
Washers. Positioning Jig for
Washers. Positioning Jig for
Installation. Insulation for
Installation. Insulation for
Hanger Bracket. Air Outlet
Hanger Bracket. Air Outlet
Blocking Pad.
Blocking Pad.
Conversion Formulae
cfm=m³/min×35.3
Specifications
FXKQ63MVE
6,300
24,900
7.3
7.1
6,900
27,300
8.0
215×1,310×710
3×11×1.75
0.226
4D12H1AJ1V1
Sirocco Fan
45×1
18/15
635/530
18/13
635/459
Direct Drive
VP25
)
Internal Dia. 25
34
42/37
Fuse.
BYK71FJW1
70×1,440×800
Resin Net
9.5
kcal/h=kW×860
Btu/h=kW×3412
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv ii rxyq8matlVrv ii rxyq8maylVrv ii rxyq5maylVrv ii rxyq5mayleVrv ii rxyq8mayleVrv ii rxyq5matle ... Show all

Table of Contents