Troubleshooting by Indication on the Remote Controller
3.41 " U2 " Outdoor Unit:
Instantaneous Failure
U2
Remote
Controller
Display
Applicable
RXYQ5MA~48MA
Models
Method of
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Detection
Malfunction
When the capacitor above only has a voltage of 380 V or less (YL).
When the capacitor above only has a voltage of 220 V or less (TL).
Decision
Conditions
Supposed
Causes
216
Power Supply Insufficient or
Power supply insufficient
Instantaneous failure
Open phase
Defect of inverter PC board
Defect of outdoor control PC board
Main circuit wiring defect
Si39-504
Troubleshooting