U2" Outdoor Unit: Power Supply Insufficient Or; Instantaneous Failure - Daikin VRV II RXYQ5MATL Service Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
3.41 " U2 " Outdoor Unit:

Instantaneous Failure

U2
Remote
Controller
Display
Applicable
RXYQ5MA~48MA
Models
Method of
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Detection
Malfunction
When the capacitor above only has a voltage of 380 V or less (YL).
When the capacitor above only has a voltage of 220 V or less (TL).
Decision
Conditions
Supposed
Causes
216
Power Supply Insufficient or
Power supply insufficient

Instantaneous failure

Open phase
Defect of inverter PC board
Defect of outdoor control PC board
Main circuit wiring defect
Si39-504
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv ii rxyq8matlVrv ii rxyq8maylVrv ii rxyq5maylVrv ii rxyq5mayleVrv ii rxyq8mayleVrv ii rxyq5matle ... Show all