Daikin VRV II RXYQ5MATL Service Manual page 151

R-410a heat pump 60hz
Table of Contents

Advertisement

Field Setting
Supplementation on
When switching cool/heat for each adapter PC board with the use of more than one adapter PC
board, set the address of the external control adaptor for outdoor unit PC board DS1 and DS2
so that it matches the unified cool/heat address of outdoor unit main PC board.
Address setting for
Address
No.
No 0
No 1
No 2
No 3
No 4
No 30
No 31
140
and
.
and
Outdoor unit PC board LED
Set with setting mode 2
87
77777
0
87
77778
1
87
77787
2
87
77788
3
87
77877
4
87
88887
30
87
88888
31
8
7
ON
OFF
(Set lower 5 digits with binary number.) [No.0 to No.31]
External control adaptor for outdoor unit
DS2
Upper position (ON)
lower position (OFF)
Si39-504
DS1
0
1
2
3
4
30
31
(The shaded part shows knob)
(V2724)
Test Operation

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv ii rxyq8matlVrv ii rxyq8maylVrv ii rxyq5maylVrv ii rxyq5mayleVrv ii rxyq8mayleVrv ii rxyq5matle ... Show all

Table of Contents