3.23 " H9 " Outdoor Unit; H9" Outdoor Unit: Malfunction Of Thermistor (R1T) For Outdoor Air - Daikin VRV II RXYQ5MATL Service Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

Si39-504

3.23 " H9 " Outdoor Unit:

Outdoor Air
H9
Remote
Controller
Display
Applicable
RXYQ5MA~48MA
Models
Method of
The abnormal detection is based on current detected by current sensor.
Malfunction
Detection
Malfunction
When the outside air temperature sensor has short circuit or open circuit.
Decision
Conditions
Supposed
Causes
Troubleshooting
The alarm indicator is displayed when the fan only is being used also.
∗ Refer to "Thermistor Resistance / Temperature Characteristics" table on P299.
Troubleshooting
Malfunction of Thermistor (R1T) for
Defect of thermistor (R1T) for outdoor air
Defect of outdoor unit PC board (A1P)
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Connector is
connected to X44A of
outdoor PC board
(A1P).
YES
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the outdoor
unit PC board.
(3.5kΩ~
360kΩ)
YES
Troubleshooting by Indication on the Remote Controller
NO
NO
Connect the connector and turn on
again.
Replace the thermistor (R1T)
Replace outdoor unit PC board
(A1P).
(V3070)
197