3.32 " L4 " Outdoor Unit; Temperature Rise - Daikin VRV II RXYQ5MATL Service Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller

3.32 " L4 " Outdoor Unit:

Temperature Rise

L4
Remote
Controller
Display
Applicable
RXYQ5MA~48MA
Models
Method of
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Detection
Malfunction
When the temperature of the inverter radiation fin increases above 98°C.
Decision
Conditions
Supposed
Causes
Troubleshooting
∗ Refer to "Thermistor Resistance / Temperature Characteristics" table on P299.
206
Malfunction of Inverter Radiating Fin
Actuation of fin thermal (Actuates above 98°C)
Defect of inverter PC board
Defect of fin thermistor
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Temperature
of the radiator fin rises.
Actuates at min.
98 ˚C
NO
Resistance
check of the radiator fin
thermistor
Normal
Is reset possible?
YES
YES
Abnormal
NO
Si39-504
Defect of power unit radiation.
• Intake port is clogged
• Radiator fin is dirty
• Outdoor temperature is high
Replace the thermistor.
Replace the inverter PC board
Reset and operate.
(V2811)
Troubleshooting