J8" Malfunction Of Oil Equalizing Pipe Thermistor (R7T) - Daikin VRV II RXYQ5MY1B Service Manual

R-410a heat pump 50hz
Hide thumbs Also See for VRV II RXYQ5MY1B:
Table of Contents

Advertisement

SiE39-404

2.28 "J8" Malfunction of Oil Equalizing Pipe Thermistor (R7T)

J8
Remote
Controller
Display
Applicable
RXYQ5~48M
Models
Method of
Malfunction is detected according to the temperature detected by oil equalizing pipe thermistor.
Malfunction
Detection
Malfunction
When the oil equalizing pipe thermistor is short circuited or open.
Decision
Conditions
Supposed
Causes
Troubleshooting
∗2: Refer to thermistor resistance / temperature characteristics table on P311.
Troubleshooting
Faulty oil equalizing pipe thermistor (R7T)
Faulty outdoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Is
the connector
for oil equalizing
pipe thermistor
connected to X37A on
outdoor unit PC
board (A1P)?
YES
Is the
resistance
measured after
removing the thermistor
(R7T) from outdoor unit PC
board normal?
(3.5 kΩ to
360 kΩ)
YES
Troubleshooting by Indication on the Remote Controller
NO
NO
Connect thermistor and operate
unit again.
Replace thermistor (R7T).
Replace outdoor unit PC board
(A1P).
(V3075)