Daikin VRV II RXYQ5MY1B Service Manual page 53

R-410a heat pump 50hz
Hide thumbs Also See for VRV II RXYQ5MY1B:
Table of Contents

Advertisement

Specifications
Ceiling Suspended Cassette Type
Indoor Unit
Model
Connection Unit
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
H5 Sound Level (H/L)
Safety Devices
Standard Accessories
Drawing No.
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference;
4 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
BEV Units
Model
Power Supply
Casing
Dimensions: (H×W×D)
Sound Absorbing Thermal Insulation
Material
Liquid Pipes
Indoor
Unit
Gas Pipes
Piping
Connection
Liquid Pipes
Outdoor
Unit
Suction Gas Pipes
Machine Weight (Mass)
Standard Accessories
Drawing No.
42
FXUQ71MV1
BEVQ71MVE
kcal/h
7,100
Btu/h
28,200
kW
8.3
kW
8.0
kcal/h
7,700
Btu/h
30,700
kW
9.0
White (10Y9/0.5)
mm
165×895×895
mm
3×6×1.5
0.265
QTS48A10M
Turbo Fan
W
45×1
m³/min
19/14
cfm
671/494
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Heat Resistant Foamed Polyethylene,
Regular Foamed Polyethylene
φ9.5 (Flare Connection)
mm
φ15.9 (Flare Connection)
mm
mm
I.Dφ20×O.Dφ26
kg
25
dBA
40/35
Thermal Protector for Fan Motor
Operation Manual, Installation
Manual, Drain Hose, Clamp Metal,
Insulation for Fitting, Sealing Pads,
Clamps, Screws, Washers, Holding
Plate.
difference: 0m.
difference: 0m.
0m. (Heat pump only)
values are normally somewhat higher during actual operation as a result of ambient conditions.
BEVQ71MVE
1 Phase 50Hz 220~240V
Galvanized Steel Plate
mm
100×350×225
Flame and Heat Resistant Foamed
Polyethylene
9.5mm (Flare Connection)
15.9mm (Flare Connection)
9.5mm (Flare Connection)
15.9mm (Flare Connection)
kg
3.0
Installation manual, Gas piping
connections, Insulation for fitting,
Sealing material, Clamps
4D045387
FXUQ100MV1
BEVQ140MVE
10,000
39,700
11.6
11.2
10,800
42,700
12.5
White (10Y9/0.5)
230×895×895
3×8×1.5
0.353
QTS50B15M
Turbo Fan
90×1
29/21
1,024/741
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Heat Resistant Foamed Polyethylene,
Regular Foamed Polyethylene
φ9.5 (Flare Connection)
φ19.1 (Flare Connection)
I.Dφ20×O.Dφ26
31
43/38
Thermal Protector for Fan Motor
Operation Manual, Installation
Manual, Drain Hose, Clamp Metal,
Insulation for Fitting, Sealing Pads,
Clamps, Screws, Washers, Holding
Plate.
4D049395
BEVQ100MVE
1 Phase 50Hz 220~240V
Galvanized Steel Plate
100×350×225
Flame and Heat Resistant Foamed
Polyethylene
9.5mm (Flare Connection)
15.9mm (Flare Connection)
9.5mm (Flare Connection)
15.9mm (Flare Connection)
3.0
Installation manual, Gas piping
connections, Insulation for fitting,
Sealing material, Clamps
4D045387
SiE39-404
FXUQ125MV1
BEVQ140MVE
12,500
49,600
14.5
14.0
13,800
54,600
16.0
White (10Y9/0.5)
230×895×895
3×8×1.5
0.353
QTS50B15M
Turbo Fan
90×1
32/23
1,130/812
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Heat Resistant Foamed Polyethylene,
Regular Foamed Polyethylene
φ9.5 (Flare Connection)
φ19.1 (Flare Connection)
I.Dφ20×O.Dφ26
31
44/39
Thermal Protector for Fan Motor
Operation Manual, Installation
Manual, Drain Hose, Clamp Metal,
Insulation for Fitting, Sealing Pads,
Clamps, Screws, Washers, Holding
Plate.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
BEVQ125MVE
1 Phase 50Hz 220~240V
Galvanized Steel Plate
100×350×225
Flame and Heat Resistant Foamed
Polyethylene
9.5mm (Flare Connection)
15.9mm (Flare Connection)
9.5mm (Flare Connection)
15.9mm (Flare Connection)
3.5
Installation manual, Gas piping
connections, Insulation for fitting,
Sealing material, Clamps
4D045388
Specifications

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents