INITIAL START-UP
q
q
q
q
CHECKING SUBCOOLING AND SUPERHEAT
Example:
Liquid line pressure =
202 PSIG converted to
minus liquid line temp.
SUBCOOLING =
The subcooling should be adjusted to 12 - 15°F (7 - 8°C).
q
SYS 1 SYS 2
Liq Line Press = ____
____
Temp = ____
____
Liq Line Temp = ____
____
Subcooling = ____
____
Example:
Suction Temp =
minus Suction Press
60 PSIG converted
to Temp
102°F (39°C)
- 87°F (31°C)
15°F
(8°C)
SYS 3 SYS 4
____
____ PSIG (kPa)
____
____ °F
(°C)
____
____ °F
(°C)
____
____ °F
(°C)
46°F (8°C)
- 34°F (1°C)
12°F (7°C)
169