Removing The System Fan 1 (Or 1&3) - Fujitsu PRIMERGY TX200 S6 Service Supplement Manual

Hide thumbs Also See for PRIMERGY TX200 S6:
Table of Contents

Advertisement

Preparation
4.1.3.2
Removing the system fan 1 (or 1&3)
Figure 4: System fan 1 and system fan 1&3
The standard system fan 1 is shorter and has just one fan cable; the redundant
system fan 1&3 (dual fan, two fans are integrated internally) is taller and has two
fan cables. The procedure for removing both system fans is identical except for
connecting the fan cables.
Figure 5: Example: Removing system fan 1&3
Ê Disconnect the fan cable from the connector FAN1 (if there is a second fan
cable, disconnect this from the connector FAN3) on the system board.
Ê Push the locking lever in the direction of the arrow (1).
Service Supplement