Product overview

2.2 Functions

2.2
Functions
IO-Link is a point-to-point connection between a master and a device. Both conventional and
intelligent sensors/actuators can be used as devices at the IO-Link via unshielded standard
cables using proven 3-wire technology. IO-Link is backward compatible to conventional
sensors. The switching state and data channels are designed with trusted 24 V DC
technology.
Reference
Additional information can be found in the IO-Link System
(https://support.automation.siemens.com/WW/view/en/65949252) function manual.
2.3

Replacing the IO-Link Master CM 8xIO-Link communication module

Master Backup
You can back up the parameters of your module with the function block
"IO_LINK_MASTER_8".
The "IO_LINK_MASTER_8" function block is used to read all relevant IO-Link device and
IO-Link Master parameters. The parameters can be stored retentively at a central location,
such as in a data block in the IO controller.
The status of the IO-Link devices or IO-Link ports stored in the IO-Link Master can be
restored with the "IO_LINK_MASTER_8" function block.
As a result, the IO-Link ports and the IO-Link Master are configured with the values stored in
the master backup.
A typical application is the restoration of parameters after replacement of the IO-Link Master.
Module
as of V 1.0
Compatibility table of the firmware versions
Note
Availability
Note that the Master Backup function is available only for IO-Link devices that are specified
for the IO-Link Standard as of V1.1.
You can find additional information on the master backup functions in the section 'Integration
into the automation system' in the IO-Link System
(https://support.industry.siemens.com/cs/ww/en/view/65949252) function manual.
12
Firmware version
Function block IO_LINK_MASTER_8
as of V 1.0.0
Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0)
Manual, 03/2019, A5E45488510-AA