Mount the Avaya G600 Media Gateway in the Rack

!
WARNING:
Make sure there is adequate ventilation in the area. The internal room temperature must
o
not exceed 43
C (110
!
WARNING:
Make sure the customer-supplied 19-inch, EIA 310D standard, open rack is properly
installed, solidly secured to the floor, and grounded. If the rack is not secured to the floor,
do not proceed with the installation. Enclosed data cabinets are not recommended, as they
may not allow sufficient ventilation to the G600 Media Gateway.
!
WARNING:
It is very important to align the media gateway with the correct holes in the frame because
the distance between each may vary. To aid your installation of the media gateway, an
actual size mounting template is included in the shipment, stored in the accessary
compartment.
Installation requires 12 inches (30 cm) of clearance in the rear and 18 inches (45 cm) of
clearance in the front for adequate ventilation, which is consistent with EIA 310D data rack
standards. In a multiple media gateway configuration, the dimensions of the TDM/LAN cable
require that one media gateway be mounted directly over the other (flush).
1
Remove the media gateway door by opening and then lifting it straight up and off the
hinge pins.
!
WARNING:
When handling circuit packs or any components of the Avaya G600, always wear an
authorized wrist ground strap connected to the ground connector provided on the system
media gateway. Store circuit packs during media gateway installation such that they will
not be damaged by electrostatic discharge.
Remove all circuit packs and the power supply.
2
3
If necessary, prepare the media gateway for mounting in the medial position by removing
the screws on the mounting brackets, moving the brackets to a position midway on the
media gateway, and re-installing the screws through the mounting bracket and into the
media gateway holes.
o
F).
May 2002
Installing the S8700 IP Connect
47