5.7

Programming analog modules

5.7
Introduction
The properties of analog modules may differ. The module properties can be programmed.
Programming tools
You program analog modules in
STOP mode.
After you defined all parameters, download these from your PG to the CPU. The CPU
transfers the parameters to the relevant analog modules at the STOP → RUN transition.
Also, position the measuring range modules of the module as required.
Static and dynamic parameters
Parameters are organized by static and dynamic properties.
Set the static parameters while the CPU is in STOP, as described earlier.
You can also modify dynamic parameters in the active user program using SFCs. However,
the parameters set in
transition of the CPU.
Parameters
static
dynamic
5.7.1

Parameters of analog input modules

Parameters of analog input modules
For information on parameters supported by specific analog modules, refer to the chapter
dealing with the relevant module.
The defaults apply if you have not set any parameters in STEP 7.
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
Representation of the analog values of analog modules
STEP 7
. Always program the module while the CPU is in
STEP 7
will be applied again after a RUN → STOP, STOP → RUN
configurable using
PG (STEP 7 HW CONFIG)
PG (STEP 7 HW CONFIG)
SFC 55 in the user program
5.7 Programming analog modules
CPU
operating state
STOP
STOP
RUN
5-31