Table 5-35 Representation Of Analog Values In The ±10 V Output Range - Siemens SIMATIC S7-300 Manual

Automation system, module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Representation of analog values in the voltage output ranges
Table 5-35
Representation of analog values in the ±10 V output range
System
dec
118,5149 %
32767
32512
117,589 %
32511
27649
100 %
27648
75 %
20736
0,003617 %
1
0 %
0
-1
-75 %
-20736
-100 %
-27648
-27649
-117,593 %
-32512
-32513
-118,519 %
-32768
Table 5-36
Representation of analog values in the 0 V to 10 V and 1 V to 5 V output ranges
System
dec
118,5149 %
32767
32512
117,589 %
32511
27649
100 %
27648
75 %
20736
0,003617 %
1
0 %
0
-1
-25 %
-6912
-6913
-117,593 %
-32512
-32513
-118,519 %
-32768
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
5.2 Representation of the analog values of analog output channels
Voltage output range
hex
±10 V
7FFF
0.00 V
7F00
7EFF
11.76 V
6C01
6C00
10 V
5100
7.5 V
1
361.7 µV
0
0 V
FFFF
-361.7 µV
AF00
-7.5 V
9400
-10 V
93FF
8100
-11.76 V
80FF
8000
0.00 V
Voltage output range
hex
0 V to 10 V
7FFF
0.00 V
7F00
7EFF
11.76 V
6C01
6C00
10 V
5100
7.5 V
1
361.7 µV
0
0 V
FFFF
E500
E4FF
8100
80FF
8000
0.00 V
Representation of the analog values of analog modules
Overflow, off power
Overshoot range
Nominal range
Undershoot range
Underflow, idle state
1 V to 5 V
0.00 V
Overflow, off power
5.70 V
Overshoot range
5 V
Nominal range
3.75 V
1 V +144.7 µV
1 V
Undershoot range
0 V
Not possible. Output value limited to 0
V.
Underflow, idle state
0.00 V