Table 5-13 Presentation Of Analog Values For Resistance Thermometers Pt 100, 200, 500,1000 Und Pt 10, 50, 100, 500 Gost (0.003850) Klima - Siemens SIMATIC S7-300 Manual

Automation system, module data
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Representation of the analog values of analog modules
5.1 Representation of the analog values of analog input channels
Presentation of analog values for resistance thermometers Pt x00 and Pt x0 GOST (0.003850)
standard
Table 5-13
Presentation of analog values for resistance thermometers Pt 100, 200, 500,1000 und Pt 10, 50, 100, 500
GOST (0.003850) Klima
Pt x00
Units
Klima/
dec
GOST in °C
(1 digit =
0.01°C)
> 155.00
32767
155.00
15500
:
:
130.01
13001
130.00
13000
:
:
-120.00
-12000
-120.01
-12001
:
:
-145.00
-14500
< - 145.00
-32768
Representation of the analog values of Ni x00 Standard resistance thermometers
Table 5-14
Representation of the analog values of Ni100, 120, 200, 500, 1000 and
LG-Ni 1000 resistance thermometers
Ni x00
Units
Standard in
dec
°C (1 digit =
0.1°C)
> 295.0
32767
295.0
2950
:
:
250.1
2501
250.0
2500
:
:
-60.0
-600
-60.1
-601
:
:
-105.0
-1050
< -105.0
-32768
5-8
Pt x00
Klima/
hexa-
GOST in °F
decimal
(1 digit =
0.01 °F)
7FFF
> 311.00
H
3C8C
311.00
H
:
:
32C9
266.01
H
32C8
266.00
H
:
:
D120
-184.00
H
D11F
-184.01
H
:
:
C75C
-229.00
H
8000
< - 229.00
H
Ni x00
Standard in
hexa-
°F (1 digit =
decimal
0.1 °F)
7FFF
> 563.0
H
B86
563.0
H
:
:
9C5
482.1
H
9C4
482.0
H
:
:
FDA8
-76.0
H
FDA7
-76.1
H
:
:
FBE6
-157.0
H
8000
< -157.0
H
Units
Range
dec
hexa-
decimal
32767
7FFF
Overflow
H
31100
797C
Overshoot range
H
:
:
26601
67E9
H
26600
67E8
Nominal range
H
:
:
-18400
B820
H
-18401
B81F
Undershoot range
H
:
:
-22900
A68C
H
-32768
8000
Underflow
H
Units
Ni x00
standard in
dec
hexa-
K (1 digit =
decimal
0.1 K)
32767
7FFF
> 568.2
H
5630
15FE
568.2
H
:
:
:
4821
12D5
523.3
H
4820
12D4
523.2
H
:
:
:
-760
FD08
213.2
H
-761
FD07
213.1
H
:
:
:
-1570
F9DE
168.2
H
-32768
8000
< 168.2
H
Units
Range
dec
hexa-
decimal
32767
7FFF
Overflow
H
5682
1632
Overshoot
H
range
:
:
5233
1471
H
5232
1470
Nominal
H
range
:
:
2132
854
H
2131
853
Underflow
H
range
:
:
1682
692
H
32768
8000
Underflow
H
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents