Valid Ip Addresses For Call Accept - Siemens 7XV5655-0BB00 Manual

Modem for transmission of serial data or protocols from devices with an rs232/rs485/fo interface via ethernet
Hide thumbs Also See for 7XV5655-0BB00:
Table of Contents

Advertisement

English

Valid IP Addresses for Call Accept

To enhance the security of the called Serial Modem, the user can restrict call acceptance
only to a number of permanently stored IP addresses.
Activating Password Configuration Mode
The settings can only be made in password configuration mode. You can enter this mode
for the first time by entering ATP<Enter>. If the master password has been changed, the
new master password must be entered.
ATP<Enter>
ATPmaster password Entry of the changed master password.
Entering / Changing / Deleting IP Addresses
In password configuration mode, you can store up to ten IP addresses in a list
(ATR0...ATR9). Any assignment is possible.
If only an IP address is assigned, calls from this IP address only are accepted.
If this list is empty (default), incoming calls from all Serial Modems are accepted.
ATR0=192.168.10.12 Calls are accepted by IP address 192.168.10.12
ATR0=<Enter>
Note: The connection via the serial RS232 interface can only be established with the
baudrate and data format currently set in the modem.
Reading IP Addresses
ATR? or ATR0?... ATR9? enable you to read individual IP addresses and AT&R all IP
addresses.
ATR0? IP address 1 is output.
AT&R All IP addresses are listed.
Saving Changes:
All changes are only applied when they are saved.
Saving is performed by entering AT&W.
AT&W
Note: If the settings are not saved, all changes are lost as soon as the Serial Modem is
disconnected from the power supply.
Ending Password Configuration Mode
After saving the settings, you must end password configuration mode again.
Entering AT&P ends configuration mode.
AT&P Ends password configuration mode
65 / 77
Entry on initial configuration.
(example).
IP address 1 is deleted
7XV5655-0BB00
C53000-G1176-C175-2

Advertisement

Table of Contents
loading