RS232 and RS485
Connection type
Pin assignment
Cable length RS232
Baud rate
DIP switches
LED displays
Firmware
Driver
Mechanical design
Housing
Dimensions
Weight:
Degree of protection acc. to EN60529
Protection class
Safety
Acc. to DIN EN61010 Part 1
Overvoltage category
Pollution degree
Fire resistance class (acc. to UL94)
70 / 77
9-way SubD connector, 4/40 UNC screw
connection
See Pin Assignment
Max. 10 m / 3280 feet
2400 to 115200 baud, Rxd, Txd
Parity : None, Even, Odd, Mark, Space
Data : 7 or 8 bits
Stop : 1 or 2 bits
RS232 : full-duplex , RS485 : half-duplex
RS232/485 switchover
Idle state FO ON/OFF
RS485 termination
DR (GN): Alarm (Vaux power o.k. and reset o.k.)
COM-TxD (GN) : Transmit - RS232 or RS485 or
FO
COM-TxD (YE) : Receive - RS232 or RS485 or
FO
System (GN) : Connection to the PC via RS232
detected
LAN-TxD (GN) : Transmit Ethernet
LAN-TxD (YE) : Receive - Ethernet
LAN (GN) : Connection to the Ethernet network
Error (RD) : modem error on RS232/Reset
Updatable
Setup & configuration tool
for WINDOWS® NT4 / 2000 / XP
Note :
To operate this modem, Windows XP Home
Edition is sufficient but for DIGSI, XP
Professional is required.
Plastic
See Dimension Drawings
Approx. 180 g
IP20 (housing and terminals)
I Protective Earth
III
2
V0
C53000-G1176-C175-2