English
Mechanical tests, vibration and shock
stress - during transport
Vibration
IEC 60255-21-1, Class 2
IEC 60068-2-6
Shock
IEC 60255-21-2, Class 1
IEC 60068-2-27
Shock
IEC 60255-21-2, Class 1
IEC 60068-2-27
Climatic tests
Recommended operating temperature
Limit temp. during operation
Limit temp. during storage
Limit temp. during transport
Humidity
Maximum relative humidity
Installation altitude
Maximum height above sea level
All devices shall be installed so that they are not exposed to direct sunlight, nor subject to great
fluctuations in temperature that may cause condensation.
73 / 77
Sinusoidal, 5 to 8 Hz : 7.5 mm ampl.
8 to 150 Hz : 2 g accel.,
20 cycles in 3 orthogonal axes
Semi-sinusoidal, 15 g accel., 11 ms duration
3 shocks each in both directions of the 3 axes
Semi-sinusoidal, 10 g accel., 16 ms duration
1000 shocks each in both directions of the 3 axes
0 °C to 55 °C
-5 °C to +70 °C
-25 °C to +55 °C (factory packing)
-25 °C to +70 °C (factory packing)
80 % at temperatures up to 31 °C,
decreasing linearly down to 50 % at 40 °C
2,000 m
C53000-G1176-C175-2
7XV5655-0BB00