Appendix A - Common Hvac Snvt's - Carrier LonWorks i-Vu Link Integration Manual

Table of Contents

Advertisement

Appendix A - Common HVAC SNVT's

Appendix A - Common HVAC SNVT's
SNVT #
SNVT Name
39
SNVT_temp
83
SNVT_state
84
SNVT_time_stamp
85
SNVT_zerospan
87
SNVT_elapsed_tm
88
SNVT_alarm
LonWorks Integration Guide
i-Vu® Link and Open Link
Element #
Measurement
0
°C
0
0
year
1
month
2
day
3
hour
4
minute
5
second
0
zero offset
1
span multiplier
0
day
1
hour
2
minute
3
second
4
millisecond
0 — 5
location
6
object ID (in node)
14
Value
-274 — 6,279.5
0 — 65,535
Each bit must be parsed out using control
program logic.
0 — 3,000
1 — 12 = January — December
0 = month not specified
1 — 31
0 = day not specified
0 — 23
0 — 59
0 — 59
-163.84% — 163.835%
0 — 32.7675
0 — 65,535
0 — 23
0 — 59
0 — 59
0 — 999
0 — 255 (decimal ASCII value)
location of node number,
description of characters used
0 — 65,535
CARRIER CORPORATION ©2018
All rights reserved

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lonworks i-vu open link

Table of Contents