Verify The Controller Is Set Up Correctly; To Capture Communication Using Putty - Carrier LonWorks i-Vu Link Integration Manual

Table of Contents

Advertisement

6 Verify the controller is set up correctly

6 Verify the controller is set up correctly
1
Verify that the latest control programs have been downloaded into the i-Vu® or Field Assistant application.
2
On the i-Vu® or Field Assistant navigation tree, select the third-party controllers for the i-Vu® Link/Open Link.
3
Select Properties page > Network Points tab.

To capture communication using PuTTY

Use PuTTY, a free open source terminal emulation program that works with all Windows operating systems, to
capture communication between the controller and the LonWorks device into a text file.
PREREQUISITES
Download and install PuTTY from the PuTTY website
(http://www.chiark.greenend.org.uk/~sgtatham/putty/download.html).
Get the Carrier control module's IP address.
Get the longest microblock refresh time in the control program that has the error you are troubleshooting. In
the i-Vu® or Field Assistant interface, view the control program's Properties page > Network Points tab to see
all the refresh times.
1
Connect your computer's Ethernet port to the control module's Ethernet port using one of the following:
A CAT5 or higher Ethernet crossover cable
A hub and a CAT5 or higher Ethernet straight-through cable
2
Ping the Carrier control module to verify communications between the control module and the computer you
are using to get this capture.
3
On the i-Vu® or Field Assistant navigation tree, right-click the controller, select Driver Properties, then select
Protocols.
4
Click Properties, select Enable Telnet diagnostics, then click Accept.
5
Start PuTTY.
6
Enter the control module's IP address.
7
Select Telnet as the Connection Type.
8
Click the Logging option in the upper left corner of the left pane.
9
Select Printable output.
10 Select a location for the capture text file.
11 Click Open to start the session.
12 After Login:>, type:
Press Enter.
LonWorks Integration Guide
i-Vu® Link and Open Link
diagport
12
CARRIER CORPORATION ©2018
All rights reserved