Special Conditions - Siemens SITRANS F Series Additional Operating Instructions

Hide thumbs Also See for SITRANS F Series:
Table of Contents

Advertisement

SITRANS FX330

3.2 Special conditions

Flameproof joints in the housing
The housing must be replaced if there is any damage to the joint area. The flameproof thread
gaps and the cylindrical joint between the terminal and the electronics compartments must be
inspected visually after opening.
WARNING!
Repairs of the flameproof joints are not allowed.
Electrostatics
For painted versions, risks due to electrostatic charge must be minimized.
For further information refer to
Thermal and electrical data
Observe the maximum ambient and product temperatures and electrical data. For further
information refer to
temperature for equipment category II 2 D
09/2018 - A5E40861058-AB
Electrostatic charge
Ambient temperature / temperature classes
www.siemens.com/flow
on page 26.
on page 16 and refer to
INSTALLATION
on page 9 and refer to
Electrical data
on page 17.