Placing tap-changer into neutral
1.
Place a 3/8" socket and ratchet on the output shaft of
the motor; rotate the motor so that the contacts and
other components are aligned in the neutral position
2.
Confirm that the regulator is in the neutral position.
A. Main movable contacts are located on the neutral
stationary contact, which is located at the 11 o'clock
position and under the reversing switch movable
contact assembly. See Figure 101.
Neutral
Stationary
Contact
Figure 101. Neutral stationary contact.
B. The reversing movable contact is located on the
reversing neutral stationary contact. See Figure 102.
Reversing
Neutral
Stationary
Figure 102. Neutral position for reversing movable.
38
QD5 QUIK-DRIVE TAP-CHANGER INSTALLATION AND MAINTENANCE INSTRUCTIONS MN225012EN March 2016
Figure 103. Neutral position for position indicator pinion
cam and holding switch.
Main
Movable
Contacts
Reversing
Movable
Contact
C. The pinion cam is pointing to the right over the
holding switch actuator. See Figure 103.
Pinion Cam
Holding Switch
Actuator