Eaton QD5 Manual page 25

Quik-drive voltage regulator tap-changer
Table of Contents

Advertisement

21. Place the self-locking nut onto the reversing segment
shaft and then tighten with a 9/16" wrench, while
holding the reversing switch assembly to prevent it
from moving. The nut should be tightened to a torque
of 180 to 192 lb-ins (20.3 to 21.6 Nm). See Figure 49.
Figure 49. Fastening reversing segment.
22. Once the work has been completed place the tap-
changer in the neutral position.
Hardware
QD5 QUIK-DRIVE TAP-CHANGER INSTALLATION AND MAINTENANCE INSTRUCTIONS MN225012EN March 2016
Placing tap-changer into neutral
1.
Place a 3/8" socket and ratchet on the output shaft of
the motor; rotate the motor so that the contacts and
other components are aligned in the neutral position
2.
Confirm that the regulator is in the neutral position:
A. Main movable contacts are located on the neutral
stationary contact, which is located at the 11 o'clock
position and under the reversing switch movable
contact assembly. See Figure 50.
Neutral
Stationary
Contact
Figure 50. Neutral stationary contact position for main
movable contacts.
B. The reversing movable contact is located on the
reversing neutral stationary contact. See Figure 51.
Reversing
Neutral
Stationary
Contact
Figure 51. Neutral position for reversing movable.
Main
Movable
Contacts
Reversing
Movable
Contact
21