Eaton QD5 Manual page 41

Quik-drive voltage regulator tap-changer
Table of Contents

Advertisement

3.
To remove a VR Reversing Stationary Contact use a
9/16" socket and ratchet to loosen and remove both the
nuts and flat washers from each of the contact studs.
See Figure 98.
Figure 98. Reassembling hardware.
4.
Remove the VR reversing stationary contact from the
contact assembly panel. See Figure 106.
Tapered Edge
Figure 99. VR reversing stationary contact removal
5.
Install the new VR reversing stationary contact into
the mounting holes in the contact assembly board.
Make sure when installing the contact that the leading
tapered edge is positioned toward the reversing neutral
stationary contact. If the tapered edge is facing in the
wrong direction, the stationary VL contact is being
used. See Figure 99.
VR Stationary
Hardware
QD5 QUIK-DRIVE TAP-CHANGER INSTALLATION AND MAINTENANCE INSTRUCTIONS MN225012EN March 2016
6.
Place a flat washer and nut on each stud. Use a 9/16"
socket and ratchet to tighten the nuts on each contact
stud. Using a torque wrench tighten the nuts to a
torque of 80–90 lb-ins (9.0–10.2 Nm). See Figures 100.
Figure 100. Removing hardware.
7 .
Once the work has been completed, place the tap-
changer in the neutral position.
VR Stationary
Hardware
37