Eaton QD5 Manual page 39

Quik-drive voltage regulator tap-changer
Table of Contents

Advertisement

Placing tap-changer into neutral
1.
Place a 3/8" socket and ratchet on the output shaft of
the motor; rotate the motor so that the contacts and
other components are aligned in the neutral position
2.
Confirm that the regulator is in the neutral position.
A. Main movable contacts are located on the neutral
stationary contact, which is located at the 11 o'clock
position and under the reversing switch movable
contact assembly. See Figure 92.
Neutral
Stationary
Figure 92. Neutral position for main movable contacts.
Main
Movable
Contacts
QD5 QUIK-DRIVE TAP-CHANGER INSTALLATION AND MAINTENANCE INSTRUCTIONS MN225012EN March 2016
B. The reversing movable contact is located on the
reversing neutral stationary contact. See Figure 93.
Reversing
Neutral
Stationary
Figure 93. Neutral position for reversing movable contact.
C. The pinion cam is pointing to the right over the
holding switch actuator. See Figure 94.
Pinion Cam
Figure 94. Neutral position for position indicator pinion
cam and holding switch.
Reversing
Movable
Contact
Holding Switch
Actuator
35

Advertisement

Table of Contents
loading

Related Products for Eaton QD5

This manual is also suitable for:

Cooper powers seriesCooper power series5740785b72er

Table of Contents