Eaton QD5 Manual page 24

Quik-drive voltage regulator tap-changer
Table of Contents

Advertisement

18. Place the mounting hardware onto the reversing logic
switches and fasten to the tap-changer front plate.
While holding a small screwdriver (or 5/32" Allen
wrench), tighten the nuts to a torque of 4–5 in-lbs (0.5–
0.6 Nm). See Figure 45.
4-40x1.25
Screws
Figure 45. Reinstalling logic switches.
19. If none is present on the threads, apply Loctite
threadlocker to the two 1/4-28 bolts. Using the bolts
and a 7/16" wrench, fasten the reversing movable
bushing to the front of the tap-changer. Tighten the
bolts to a torque of 30–40 in-lbs (3.4–4.5 Nm). See
Figure 46.
Hardware
Figure 46. Reinstalling bushing.
20
QD5 QUIK-DRIVE TAP-CHANGER INSTALLATION AND MAINTENANCE INSTRUCTIONS MN225012EN March 2016
20. Place the reversing segment arm onto the reversing
4-40
Hex
Nut
Reversing
Logic
Switches
Figure 47. Installing reversing segment arm.
®
243™
Bushing
Figure 48. Positioning the reversing movable with the
bushing.
actuator shaft. Align the square portion of the shaft
with the square hole in the arm. If needed, place a
screwdriver through the movable contact tube and push
the shaft forward while seating the arm over the shaft.
It may be necessary to rotate the movable contact
assembly slightly to align the shaft and hole. See
Figures 47 and 48.
Reversing Segment Arm
Shaft

Advertisement

Table of Contents
loading

Related Products for Eaton QD5

This manual is also suitable for:

Cooper powers seriesCooper power series5740785b72er