Eaton QD5 Manual page 18

Quik-drive voltage regulator tap-changer
Table of Contents

Advertisement

18–20 lb-in
(5–2.2 Nm)
Figure 25. Motor to mounting bracket torque
requirements.
Figure 26. Motor pivot stud and locknut torque
requirements.
14
QD5 QUIK-DRIVE TAP-CHANGER INSTALLATION AND MAINTENANCE INSTRUCTIONS MN225012EN March 2016
180–192 lb-in
(20.2–21.6 Nm)
65–75 in-lbs
(7.5–8.5 Nm)
Figure 27. Geneva gear torque requirements.