Eaton QD5 Manual page 35

Quik-drive voltage regulator tap-changer
Table of Contents

Advertisement

3.
Remove the stationary contact from the contact
assembly panel. See Figure 79.
4.
Install the new stationary contact into the mounting
holes in the contact assembly board for the contact
being replaced. See Figure 80.
Figure 80. Stationary contact removal.
5.
Place a flat washer and nut on each stud. Use a 9/16"
deep-well socket and ratchet to tighten the nuts. Using
a torque wrench, tighten the nuts to a torque of 80–90
in-lbs (9.0–10.2 Nm). See Figure 81.
Washer
Figure 81. Contact hardware installation.
Nut
QD5 QUIK-DRIVE TAP-CHANGER INSTALLATION AND MAINTENANCE INSTRUCTIONS MN225012EN March 2016
6.
Repeat Steps 1 through 5 for each stationary contact to
be replaced.
7 .
When the movable contacts are located on the
stationary contact to be replaced, the movable contacts
must be moved. Place a 3/8" socket onto the rear shaft
of the motor. See Figure 82. Using a ratchet, rotate
the motor to position the movable contacts off of the
contact to be replaced.
3/8" Socket and
Ratchet
Back Side of
Contact Panel
Figure 82. Motor and movable contact rotation.
8.
Once the work has been completed, place the tap-
changer in the neutral position.
Motor Shaft
31