Viessmann VITODENS 222-F Installation And Service Instructions Manual page 82

Gas condensing storage combi boiler
Table of Contents

Advertisement

Troubleshooting
Fault messages
(cont.)
Fault number
System characteristics
on the display
F.380
Burner in a fault state
F.381
Burner in a fault state
F.382
Burner in a fault state
F.383
Burner in a fault state
F.384
Burner in a fault state
F.385
Burner in a fault state
F.386
Burner in a fault state
F.387
Burner in a fault state
F.388
Burner in a fault state
F.395
Burner in a fault state
F.396
Burner in a fault state
F.399
Burner in a fault state
82
Cause
Flame is lost immediately
after flame formation (dur-
ing safety time).
Flame loss during stabili-
sation or operating phase
Error counter has excee-
ded limit.
Gas valve does not close.
Gas valve does not close.
Short circuit, signal 1, ioni-
sation current
Lead break, signal 1, ioni-
sation current
Short circuit, signal 2, ioni-
sation current
Lead break, signal 2, ioni-
sation current
Short circuit, flame tem-
perature signal 1
Lead break, flame temper-
ature signal 1
Short circuit, ionisation
voltage, signal 1
Measures
Check gas supply (gas pressure
and gas flow switch).
Check balanced flue system for
flue gas recirculation.
Check ionisation electrode for the
following:
Distance to burner gauze assem-
bly (see page 43)
Contamination on electrode
Reset the appliance.
Check gas supply (gas pressure
and gas flow switch).
Check balanced flue system for
flue gas recirculation.
Check ionisation electrode for the
following:
Distance to burner gauze assem-
bly (see page 43)
Contamination on electrode
Reset the appliance.
Reset the appliance.
Check the gas train, replace if nec-
essary.
Reset the appliance.
Check the gas train, replace if nec-
essary.
Reset the appliance.
Check ionisation electrode and
connecting cable.
Reset the appliance.
Check ionisation electrode and
connecting cable.
Reset the appliance.
Check ionisation electrode and
connecting cable.
Reset the appliance.
Check ionisation electrode and
connecting cable.
Reset the appliance.
Check ionisation electrode and
connecting cable.
Reset the appliance.
Check ionisation electrode and
connecting cable.
Reset the appliance.
Check ionisation electrode and
connecting cable.
Reset the appliance.