Viessmann VITODENS 222-F Installation And Service Instructions Manual page 58

Gas condensing storage combi boiler
Table of Contents

Advertisement

System configuration (parameters)
Boiler
(cont.)
522.3 "Interval until the next service"
Setting
1411.0 "Clear maintenance messages"
Setting
No
Yes
596.0 "Maximum heating output"
Setting
597.0 "Limit, max. heating output for DHW heating"
Setting
1100.2 "Set speed of the primary circuit pump in heating mode"
Setting
1432.1 "Residual head control of primary circuit pump"
Setting
58
Explanations
Interval until the next service
0
No interval selected
1
3 months
2
6 months
3
12 months
4
18 months
5
24 months
Explanations
Clear maintenance messages once maintenance has
been performed.
0
Maintenance messages are active (if present).
1
Clear maintenance messages once.
Explanations
A limit can be set on the maximum heating output for
heating mode.
100
Heating output in the delivered condition 100 %
0 to 100
Adjustable from 0 to 100 %
Explanations
A limit can be set on the maximum heating output for
DHW heating.
100
Heating output in the delivered condition 100 %
0 to 100
Adjustable from 0 to 100 %
Explanations
Set speed of internal circulation pump
In heating mode
With external demand
With demand in conjunction with a low loss header
...
Delivered condition specified by settings specific to
the appliance
20 to 100
Set speed adjustable from 20 to 100 %
Explanations
Residual head limit value for reducing pump speed of
the internal circulation pump, in mbar
0
Internal circulation pump is controlled in line with the
outside temperature
1 to 255
Internal circulation pump is operated with constant re-
sidual head.
Recommended setting: 120 mbar
1 step
1 mbar