Commissioning, inspection, maintenance
Checking the combustion quality
Permissible CO
or O
2
Operation with natural gas
Rated heating out-
CO
put (kW)
Upper heating out-
put
11
7.3 - 10.5
19
7.5 - 10.5
25
7.5 - 10.5
32
7.3 - 10.0
Operation with LPG
CO
content: 8.4 - 11.8 %
2
O
content: 3.1 - 8.1 %
2
If the actual CO
or O
values lie outside their respec-
2
2
tive ranges, proceed as follows:
Check the balanced flue system for tightness; see
page 40.
Check ionisation electrode and connecting cable.
Note
During commissioning, the combustion controller car-
ries out an automatic calibration. Only measure the
emissions approx. 50 s after the burner has started.
1. Connect a flue gas analyser at flue gas port
the boiler flue connection.
2. Open the gas shut-off valve. Start the boiler. Cre-
ate a heat demand.
3. Adjust the lower heating output. See the following
chapter.
4. Check the CO
content. If the actual value deviates
2
from the permissible ranges, implement steps lis-
ted above.
5. Enter the actual value into the report.
Setting the upper/lower heating output
Note
Ensure adequate heat transfer.
Tap the following buttons:
01.
and OK – press simultaneously for approx. 4 s,
then release.
02. Use
/
to select "Actuator test".
52
content
2
content (%)
2
Lower heating out-
put
7.5 - 10.5
7.5 - 10.5
7.5 - 10.5
7.5 - 10.5
A
(cont.)
O
content (%)
2
Upper heating out-
put
2.1 - 7.9
2.1 - 7.6
2.1 - 7.6
3.1 - 7.9
Fig. 45
on
6. Adjust the upper heating output. See the following
chapter.
7. Check the CO
2
from the permissible ranges by more than 1 %,
implement steps listed above.
8. Enter the actual value into the report.
9. Re-seal test port
Danger
Escaping flue gas can damage your health.
Check test port
03. OK
04. Use
/
to select the "Heating" group.
05. OK
06. Use
/
to select "Primary circuit pump,
speed".
Lower heating out-
put
2.1 - 7.6
2.1 - 7.6
2.1 - 7.6
2.1 - 7.6
A
content. If the actual value deviates
.
A
for leaks.
A