Troubleshooting
Fault messages
(cont.)
Fault number
System characteristics
on the display
F.346
Burner in a fault state
F.348
Burner in a fault state
F.349
Control mode
Burner is operating with a
limited modulation range.
F.350
Burner in a fault state
F.351
Burner in a fault state
F.352
Burner in a fault state
F.353
Burner locked out
F.354
Burner in a fault state
76
Cause
Ionisation current calibra-
tion error
Gas modulation valve
Air mass rate flow not de-
tected correctly in fan unit.
Ionisation voltage lies out-
side the permissible range
Ionisation current lies out-
side the permissible range
CO limit within appliance
exceeded.
Insufficient gas supply,
burner output reduced.
Gas modulation valve tol-
erance outside permissi-
ble range
Measures
Check the gas supply pressure.
Check gas train strainer on the
inlet side for contamination.
Check ionisation electrode for
contamination.
Check gap between ionisation
electrode and burner gauze as-
sembly (see page 43).
Reset the appliance.
Check flue system; remove flue
gas recirculation if required.
Check the connecting cable to
the fan unit.
Check impeller for ease of opera-
tion.
Reset the appliance.
Check connecting cables to the
gas train for damage.
Check the flue system for flue gas
back pressure.
Check gas train.
Reset the appliance.
Check mass flow sensor on the fan
unit. Check the flue system for flue
gas back pressure.
Check ionisation electrode and
connecting cable.
Reset the appliance.
Check ionisation electrode and
connecting cable.
Reset the appliance.
Check entire flue gas path for the
following:
Flue gas recirculation
Leaks
Flue gas back pressure caused
by water pocket (if flue system
fall is insufficient)
Constrictions
Blockages
Repair flue system if necessary.
Reset the appliance.
Check the gas supply.
Optically check input-side screen
in the gas train for contamination.
Reset the appliance.
Check connecting cables to the
gas train for damage.
Check gas train.
Check the flue system for block-
ages or constrictions.
Reset the appliance.