Viessmann VITODENS 222-F Installation And Service Instructions Manual page 81

Gas condensing storage combi boiler
Table of Contents

Advertisement

Fault messages
(cont.)
Fault number
System characteristics
on the display
F.377
Burner in a fault state
F.378
Burner in a fault state
Cause
Post-processing ionisation
current calibration: Stabili-
sation conditions for post-
calibration not reached
Flame loss during stabili-
sation or operating phase
Troubleshooting
Measures
Check ionisation electrode and
connecting cable. Check plug-in
connections for loose contacts.
Check flue system; remove flue
gas recirculation if required.
Check system for condensate
backup.
Visually inspect gas train inlet and
strainer on the inlet side for con-
tamination.
Note
To prevent water damage, detach
fan unit before removing the burn-
er.
Note
Deposits on the electrodes indicate
foreign bodies in the combustion
air. Check the installation room and
flue system for causes of the de-
posits. For example: Laundry de-
tergents, cleaning agents, toilet-
ries, deposits in the ventilation air
supply (chimney).
If burner gauze assembly and ioni-
sation electrode have been re-
placed, also clean fan unit, gas/air
channel and Venturi extension.
Reset the appliance.
Check gas supply (gas pressure
and gas flow switch).
Check gas train.
Check system for condensate
backup.
Note
To prevent water damage, de-
tach fan unit before removing the
burner.
Check ionisation electrode and
connecting cable.
Check ignition:
Connecting cables to ignition
module and ignition electrode
Ignition electrode clearance and
contamination.
Check ignition electrode for bro-
ken ceramic.
Reset the appliance.
81