Instructions for fitting connectors, attachments and devices
2.3 Electrical networks
4. Wrap copper band around the braided shield.
5. Fit the connector
50
– Fit the connector insert into the connector casing
– Fit the lower cable clamp into the grooves of the connector casing
– Match the wire pairs to the screw terminals
You will find the assignment required for a particular cable type in the section
Connector pinout (Page 46).
– Fit the cable into the connector casing so that the braided shield with the copper band
lies in the cable clamp
– Fit the upper cable clamp into the grooves of the connector casing and screw it tight
– Secure the conductors in the screw terminals
– Screw the cover on to the connector casing
Figure 2-2
9-pin D-sub plug fitted to the standard cable
5 9 1 6
System Manual, 02/2013, C79000-G8976-C282-01