Optional Night Setback - Greenheck IGX Series Installation, Operation And Maintenance Manual

Make-up air unit
Table of Contents

Advertisement

Potentiometer Recirculation Control
• Power passes to inlet damper which opens.
• When damper is fully opened, normally open
damper limit switch (DL1) closes.
• Power passes to and energizes supply starter relay
(RF).
• Power passes to normally open fan contact (RF),
which is energized and closed. Power reaches and
energizes supply fan.
• The potentiometer will output a 2-10 VDC signal
to the recirculation damper actuator to control
recirculation damper position.
External Signal Recirculation
• Power passes to inlet damper which opens.
• When damper is fully opened, normally open
damper limit switch (DL1) closes.
• Power passes to and energizes supply starter relay
(RF).
• Power passes to normally open fan contact (RF),
which is energized and closed. Power reaches and
energizes supply fan.
• An external source will provide a 2-10 VDC or
4-20 mA signal to the recirculation damper
actuator to control recirculation damper position.
Building Pressure Recirculation Control
• Power passes to inlet damper which opens.
• When damper is fully opened, normally open
damper limit switch (DL1) closes.
• Power passes to and energizes supply starter relay
(RF).
• Power passes to normally open fan contact (RF),
which is energized and closed. Power reaches and
energizes supply fan.
• The photohelic building pressure controller will
monitor the pressure differential between the
pressure in the controlled space and the pressure
outside the controlled space.
• If the pressure differential is below the set point
range established on the photohelic controller,
the recirculation damper will be modulated further
closed.
• If the pressure differential is above the set point
range established on the photohelic controller,
the recirculation damper will be modulated further
open.
• If the pressure differential is within the set point
range established on the photohelic controller,
the recirculation damper will remain in its current
position.
®
Sequence of Operation

OPTIONAL NIGHT SETBACK

Night Setback Schedule
• The night setback schedule is established within
Night Setback Fan Control
• During occupied hours, the fan sequence of
• During unoccupied hours the fan is turned off.
• If there is a call for heating from the space
• When the call for heating from the space
Night Setback Heat Control
• During occupied hours, the heating sequence of
• During unoccupied hours, the unit is off until there
• When the call for heating from the space
Night Setback Variable Volume Control
• During occupied hours, the variable volume
• When the call for heating from the space
Night Setback Recirculation Control
• During occupied hours, the recirculation sequence
• During unoccupied hours, the unit is off until there
• When the call for heating from the space
the programmable thermostat on the remote
panel. The schedule must be set for the occupied
and unoccupied hours of the controlled space.
operation is the same as that described in the
"Supply Fan" section.
thermostat, the fan will be turned on to allow for
tempering operation.
thermostat ends, the fan will be turned off.
operation is the same as that described in the
"Heat" sections.
is a call for heating from the space thermostat.
When the unit is enabled by a call for heat from
the space thermostat, the heat is also enabled
and the discharge temperature overridden to a
maximum value to provide the maximum amount
of heat to the space.
thermostat ends, the unit will be turned off.
sequence of operation is the same as that
described in the "Optional Variable Volume"
section.
During unoccupied hours, the unit is off until
there is a call for heating from the space
thermostat. When the unit is enabled by a call for
heat from the space thermostat, the supply fan
will run at minimum speed.
thermostat ends, the unit will be turned off.
of operation is the same as that described in the
"Optional Recirculation" section.
is a call for heating from the space thermostat.
When the unit is enabled by a call for heat from
the space thermostat, the recirculation damper
will be opened to provide a maximum amount of
recirculated air to the unit.
thermostat ends, the unit will be turned off.
Model IGX Make-Up Air
35