Display (Anz); Close-And-Retain System (Fsa) Control Facility And Fire Section Control Facility; Detector Display And Event Display Control Pattern; Table 24: Monitored Control Lines - Siemens SIGMASYS C Manual

Multifunctional danger control and indicating panels
Table of Contents

Advertisement

10 Programming of control facilities
Resistance
in ohms
Load
40 – 95
90 – 250
250 – 550
500-1000
950-2400
2000-4000
300 – 700
500 – 1000
900 – 2000
2000 – 5000

Table 24: Monitored control lines

The maximum line resistance must not exceed 10 % of the load resistance.
10.1.5

Display (ANZ)

The actuators in the Display category serve as indicators for the status of detectors, detector
zones or outputs
Display is mainly used for programming detector outputs when connecting detector shunt dis-
plays and for the indicator panel control facility SPF 3200.
The source (e. g. detector objects, alarm zones, detector zones, detectors or actuator statu-
ses) that tripped a display can be established for every facility. Operators can also choose
from a number of different control patterns. It is thus possible to vary the signalling criteria
(alarm, prewarning, prealarm, fault, signal) and the activation form (static, flashing or dy-
namic).
Displays cannot be activated by command. Displays cannot be tripped in operating panel
lists.
10.1.6

Close-and-retain system (FSA) control facility and fire section control facility

FSA
The FSA control facility is an inverse-operated output that is released in the event of a fault. It
is released in the event of an alarm, signal, fault, inspection, disablement of the activating de-
tector. It is also command-driven. The close-and-retain equipment is connected via the con-
trol module SPF 5100 to a detector output of a SIGMASYS detector.
The control module requires and external power supply unit.
Fire section control facility
Tripped in the event of an alarm (including an initial alarm), signal, fault, prealarm, source di-
sablement, output disablement. It is manually activated.
10.1.7

Detector display and event display control pattern

Actuators of this type can only be tripped by sources that are connected to the same module.
64 / 128
Monitoring current in mA
Monitoring input
Transponder-
output ST
50
20
8
4
2
1
0
Remark
Voltage and current in case of control
* with UB= 24V
Output voltage=UB Current 0,26-0,6A*
Output voltage =UB Current 0,096-0,266A*
Output voltage =UB Current 43mA-96mA*
Output voltage =UB Current 24mA-48mA*
Output voltage =UB Current 10mA-25mA*
Output voltage =UB Current 6mA-12mA*
6
Output voltage 20V
4
Output voltage 20V
2
Output voltage 20V
1
Output voltage 20V
0
No fault monitoring
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Current 40mA-66mA
Current 25mA-40mA
Current 10mA-28mA
Current 4mA-10mA
BMT Project Planning Guidelines