Ev - Evacuation Alarm (Internal Alarm); Control Facility (St); Monitored Control Lines According To Vds Via Transponder Spf 3500 - Siemens SIGMASYS C Manual

Multifunctional danger control and indicating panels
Table of Contents

Advertisement

It is possible to parameterise whether the alerting facility is to be tripped when the door is
open in the control and indicating panel that detected the alarm (detector zone type).
The activation list of an alarm should only contain objects that enable the "local alarm on/off"
operation to be performed from the operating panel or fire brigade operating panel.
10.1.2
EV – Evacuation alarm (internal alarm)
The evacuation alarm is used to evacuate endangered parts of buildings.
Evacuation alarm type actuators cannot be deactivated or activated with the operating panel
button "LA on/off". The function of the "Acoust. signals off" button on the fire brigade operat-
ing panel is the same as in the alerting facility.
The evacuation alarm can be activated or reset by command at any time.
The commands "EV on" and "EV off" activate and deactivate the evacuation alarm as long as
the activating alarm is available.
The operator can select which sources can activate the evacuation alarm (detector objects
and detector zones). The tripping criteria are alarm.
In the detector zone types, the operator can select whether the evacuation alarm should be
tripped when the door is open in the control and indicating panel that detected the alarm.
The significance of the evacuation alarm is reduced by the fact that the alerting facility is also
used in the meantime for evacuation purposes. It is required in certain Federal states where
the applicable building and construction law requires that acoustic evacuation alarm should
only be deactivated by authorised personnel (i. e. not via a button or in command level 2).
10.1.3

Control facility (ST)

The actuators in the control facility category are used for activating and deactivating control
equipment in response to certain signals
The source (e. g. detector objects, alarm zones, detector zones, detectors or actuator states)
that tripped the control facility can be established for every facility. Operators can also choose
from a number of different control patterns. It is thus possible to vary the signalling criteria
(alarm, prewarning, prealarm, signal) and the activation form (static, flashing or dynamic).
A control facility can also be enabled and disabled or activated and reset via a command at
the operating panel.
A control facility can be monitored for tripping or fault (monitored control facility).
In the detector zone types, the operator can select whether the control facility should be trip-
ped when the door is open in the control and indicating panel that detected the alarm.
10.1.4

Monitored control lines according to VdS via transponder SPF 3500

Only possible with firmware Version ≥ 2.6.
The monitoring current of the monitored control line must be aligned with the load resistance
in order to be able to guarantee the measuring accuracy of the various loads.
Same applies for the monitoring input of control facilities with monitoring input.
The setting is made in SIGMAPLAN when parameterising the control facility and the monitor-
ing input.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules)
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
10 Programming of control facilities
63 / 128