5 Interfaces
Spur operating panels can be connected to all V.24 interfaces in the SIGMASYS control and
indicating panel and operating panels.
Spur operating panels cannot be connected to spur alarm control and indicating panels.
The SIGMANET operating panel or the GMA operating panel can be connected as spur op-
erating panels. If possible, SIGMANET operating panels should always be connected to the
SIGMASYS standalone control and indicating panels with SIGMANET, for redundancy rea-
sons.
N.B.: A spur operating panel which has been programmed as a local operating
panel does not display faults with the connection.
5.3.2

D100 Interfaces (Version 3.0 and later)

In Version V3.0 and later, SIGMASYS control and indicating panels can be coupled with
D100 control and indicating panels without SIGMALINK. In this coupling form, the control mo-
dule in level 1 (K01) is the head of the system where all messages are accumulated. Connec-
tion to a D100 control module is via an available V.24 interface on SIGMASYS C, M, M mod-
ule or SIGMASYS operating panel.
A maximum of 99 units can operated using the D100 system. Control modules, as well as all
SIGMANET units and SIGMANET operating panels, even if they are being operated as spurs,
are included in this figure. GMA operating panels are not included.
A total of 8 SIGMANETs, each with 16 units, can be connected to an control module at level 1
(K01).
A total of 8 SIGMANETs, each with 8 units, can be connected to an control module at level
(e.g. K10 – K80).
A total of 8 SIGMANETs, each with 2 units, can be connected to an control module at level
(e.g. K11 – K88).
IMPORTANT!
If additional S modules are connected on the same level, this reduces the number of
possible SIGMANET connections by the number of connected S modules.
The number of units on a core on the second level may be reduced depending on the
number of objects. (see project planning instructions D100,
order number: A24205-A334-A846 each in their current versions).
ÜE and ÖA may not be operated by means of general system control.
Control must come from the source upwards to the K01.
VdS certified systems
Both SIGMASYS and D100 control and indicating panels must be installed in VdS certified
systems in the same cabinet or in the area adjacent to the cabinet (the same room). For best
results, install a S module and an M module in a D100 cabinet. To do this, a dual MAP is re-
quired for the control module and a dual SOC for the M module. A TTY/V.24 coupler at the
MAP's TTY interface is used for the interface connection. A redundancy line is required for
alarm transceiver control between the control module and M module.
All SIGMANET units and SIGMANET operating panels in spur mode must be upgraded
to version V3.0 if they are to be coupled to D100.
N.B.: Object and zone number allocation is limited when using D100 coupling.
28 / 128
BMT Project Planning Guidelines
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)