Siemens SIGMASYS C Manual page 47

Multifunctional danger control and indicating panels
Table of Contents

Advertisement

N.B.:
The function of the fire brigade operating panel is always permanently linked to the ob-
jects of the first AT.
The FBF must be connected to the same control and indicating panel as the alarm
transceiver.
All detector groups which activate the AT must be powered by separate objects.
Signals which do not trigger the AT should be located on separate objects.
If this system is not followed, the AT may not be actuated.
As long as an event from the object actuating the AT persists, the AT will not be actuated
again.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules)
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Deactivated control in case of fire
7 Control unit connections
39 / 128

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sigmasys m

Table of Contents