Control modules
9.3
E3G050 Control module 'Contacts'
Pos.
Module
1
Programming switch 'S3': I-Bus address
2
Maintenance switch 'S2': Activate test LEDs
'H1'....'H8'
9.4
E3G060 Control module 'monitored'
Pos.
Module
1
Programming switch 'S3': I-Bus address
2
Maintenance switch 'S2': Activate test LEDs
'H1'....'H6'
3
Programming switch 'S6': Activation 'Emer-
gency alarm'
4
0Ω resistor 'X12': Supply of the horn outputs Re-solder if necessary, i.e. in case of external
20
Building Technologies
Fire Safety & Security Products
Preparation
Set according to the system documentation
(1... 14)
Set to 'ON' for commissioning
S3
1
S2
2
Preparation
Set according to the system documentation
(1... 14)
Set to 'ON' for commissioning
Set according to the system documentation, see
description in document 007831
horn supply; see description in document
007831
1
S6
S3
X12
S2
4
2
H1
H8
H1
H6
3
Default
Address 0
To 'OFF'
Default
Address 0
To 'OFF'
To 'OFF' (control lines activated
when 'Emergency alarm')
Inserted in 'X12'
007828_b_en_--