Power Supply; B2F020 Converter; E3C011 Battery Charging Module - Siemens FC700A Installation And Hardware Commissioning

Fire detection system
Hide thumbs Also See for FC700A:
Table of Contents

Advertisement

13

Power supply

13.1

B2F020 Converter

Pos.
Module
1
Metal shield
2
Jumper
3
Metal shield
4
Converter (power unit)
5
24 supply line (enclosed in the cable set
Z3I470)
6
Mains cable
Connection cable from mains, series fuse
≤ 10A / IEC950 10 kg strain relief
13.2

E3C011 Battery charging module

Pos.
Module
1
Programming switch 'S3': I-Bus address
2
Programming switch 'S2': Select battery
type
Building Technologies
Fire Safety & Security Products
Preparation
Dismantle
Important: Check voltage set, if necessary,
change when mains voltage 115VAC
Mount again
Mount in the housing
Connect to the converter, connect to terminal
block 24V load
Connect to the converter, fix at cable clamp and
connect on mains input terminals
4
6
Mains
24V load
5
230VAC
Preparation
Set address to 16 if used in FC700A
Set address to 0 by using as auxiliary power
supply (in separate housing)
Set to the battery type used, see description in
document 007831
1
2
S3
S2
1,3
2
115VAC
Power supply
Default
Mounted
Mains voltage 230VAC
Default
Address 0
Type 'ALARMCOM' (FIAMM)
007828_b_en_--
09.2008
29