Control Contacts - Siemens Synova FC330A Manual

Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

6.6

Control contacts

FC330A / K3M010
CONTROL
Pluggable terminal block K4/K14
Alarm contact 1 or 3
(active until reset)
Alarm contact 2 or 4
(active until reset)
112
Building Technologies
Fire Safety & Security Products
1
NO
2
NC
3
C
4
NO
5
max. 30V / 1A
NC
6
C
Characteristics
Designed as dry changeover contacts
Active in alarm condition
Operating functions per control line (via menu)
− ON/OFF switching
− Activation (test)
Programmable functions per control line
− Detector zone (alarm) from which 'alarm contact' 1...4 is to be activated
− Active on 'internal' and 'external' alarm or only on 'external' alarm
Technical data
Contact rating
external system
+
Load
max. 30V / 1A
max. 1A/30V
DC
1583_o_en_−−_6
08.2005