Lon Module; E3I040 I-Bus/Lon Module - Siemens FC700A Installation And Hardware Commissioning

Fire detection system
Hide thumbs Also See for FC700A:
Table of Contents

Advertisement

LON module

8
LON module
8.1

E3I040 I-Bus/LON module

Pos.
Module
1
Programming switch 'S3': I-Bus address
2
Resistor 'R60': line termination element
'LON-Bus'
3
Jumper 'X30': Ground fault monitoring unit
'LON-Bus'
18
Building Technologies
Fire Safety & Security Products
Preparation
Set according to the system documentation
(1... 14)
If the LON-Bus is wired as "free topology", 'R60'
must be changed to 50Ω, see description in
document 007831
Ground fault monitoring -> see chapter 14
Set as described in document 007831, chapter
'Ground fault monitoring'
2
3
X30
1
S3
R60
Default
Address 0
100Ω
Removed (inactive)
007828_b_en_--
09.2008