Install Modules - Siemens FC700A Installation And Hardware Commissioning

Fire detection system
Hide thumbs Also See for FC700A:
Table of Contents

Advertisement

15

Install modules

Building Technologies
Fire Safety & Security Products
NOTE
Do never connect the I-Bus from other stations together!
Procedure:
1. Install modules in accordance with the system documentation and fix them
2. Attach I-Bus flat cable (1) (ensure good contact)
3. Attach supply cable (2). Be aware that the I-Bus supply is wired correct
Never connect or disconnect the flat cable and the supply cable when power
NOTE
supply is switched on!
E3C011
E3G070
E3M111
4. Attach battery cable
5. Attach temperature sensor to battery
6. Electrically isolate controls (e.g. remove relays from base)
7. Remove module chassis from the housing front panel and install it in the housing
When switching off for brief periods, remove the mains fuse (if available) or
NOTE
remove minus potential from power unit and minus potential battery.
E3C011
red
4
green
3
K1
blue
2
blue
1
K1
4
1
2
1
Z3I380
to additional I-Bus modules
Install modules
B3Q700 (FC)
1
2
K1
3
4
B3Q700 (FC)
1
K1
4
007828_b_en_--
31
09.2008