Pdp Specifications - Alcatel-Lucent 1675 LambdaUnite Installation And System Turn-Up Manual

Multiservice switch (mss)
Table of Contents

Advertisement

Mechanical installation
Technical data for PDP
...................................................................................................................................................................................................................................
Specifications
The Power Distribution Panel (PDP) is already pre-mounted on the rack frame and has
the specifications as given in the table below.
Table 3-5
Item
Power consumption (subrack),
Circuit breakers
Voltage range
(all components)
Power feeds
Ground
Dimensions (HxWxD)
...................................................................................................................................................................................................................................
3-54

PDP specifications

Quantity / Size
Release 1.0 and 2.0:
max. 2700 W
68 A circuit breakers must be used in the External
Battery and Fuse Bay (BDFB)
63 A circuit breakers (located on the power interfaces).
Release 2.1 and higher:
max. 3500 W
Circuit breakers ≥ 125 A must be used in the External
Battery and Fuse Bay (BDFB)
100 A circuit breakers are part of the subracks.
They are located on the power interfaces (PI/100) and are
designed to support a maximum rated current of 100 A
with a BS characteristic (medium delay). They provide
protection according to EN 60950 in the power range up
to 3500 W, in particular in the range of 87.5 – 48.6 A at
40 – 72 V.
Release 6.1 and higher:
"Breaker-less" PIs (PI/100 NOCB) can be used as an option.
In that case the subrack must be protected via an external
circuit breaker which can be located in the BDFB or on a
separate PDP. The current rating depends on the
configuration of the subrack.
-48 to -60 V battery voltages
(-40.5 V minimum, -72 V maximum)
3 power feeders (only 2 are necessary for one rack)
3 ground-connection points (only 2 are necessary for one
rack)
70 mm [2.756"] x 482.6 mm [19"] x 60 mm [2.362"]
Alcatel-Lucent - Proprietary
See notice on first page
365-374-179R10.0
Issue 2, June 2009

Advertisement

Table of Contents
loading